ArtikelHow To Contain Your Currents : Use Gradient Guards and Charge Channels  
Oleh: Anderson, K. F.
Jenis: Article from Bulletin/Magazine
Dalam koleksi: IEEE Instrumentation & Measurement Magazine vol. 1 no. 3 (1998), page 24-27.
Topik: Temperature Gradient; gradient guards; channels
Ketersediaan
  • Perpustakaan Pusat (Semanggi)
    • Nomor Panggil: II47.1
    • Non-tandon: 1 (dapat dipinjam: 0)
    • Tandon: tidak ada
    Lihat Detail Induk
Isi artikelThe classical driven - guard principle applies only to electronic circuit regions that contain a single potential. But a driven outer shield can effectively guard regions within an inner shield that contain a potential gradient. The gradient - guard configuration contains charges within an inner guard and the charge - channel configuration assures that the current entering a conductor at one end will all exit the conductor at its other end even when the conductor and its shields are imbedded in poor insulation resistance to ground.