ArtikelPerencanaan Sistem Pengadaan Air Bersih pada Bangunan Gedung Fakultas Teknik UPN "Veteran" Jakarta dengan Menggunakan Pompa  
Oleh: Siagian, Saut
Jenis: Article from Journal - ilmiah nasional
Dalam koleksi: Bina Widya: Majalah ilmiah UPN "Veteran" Jakarta vol. 26 no. 02 (May 2015), page 70-74.
Topik: clean water; dirty water; pipe ven
Ketersediaan
  • Perpustakaan Pusat (Semanggi)
    • Nomor Panggil: BB24
    • Non-tandon: 1 (dapat dipinjam: 0)
    • Tandon: tidak ada
    Lihat Detail Induk
Isi artikelConstruction of a building planned for the installation of clean water with clean water source comes from deep wells, with discharge of 7.5 liters / second. Installing a water tank roof is planned with the use of dirty water while using a separate system. Installation path using the gravitational system of pipes and pumps with a slope of 1.5 to 5%. Shower pressure ± 1bar each sanitary appliance, according to the height of each floor of shower pressure greatly affect the installation path through the line shaft. Tank capacity of 11m3 and reach the bottom of the tank capacity reached 17.02 m3Total discharge at the pump boster used dependingon the requirement that reached its peak hours of 2.44 liters / second. Vertical pipe is planned by using wet vendors, system vendors directly and dirty water which flowed into a septic tank space. Sewerage can be calculated using the average value of the number of residents who use potable water facilities have been planned to reach capacity of 100.38 liters / day.