ArtikelAnalisis Penggunaan Autotrafo Penggeser Fasa Sebagai Minimisator Harmonisa Arus di Sistem Distribusi Tenaga Listrik  
Oleh: Syafrudin ; Dahono, Pekik A. ; Sukisno ; Soelaiman, T.M.
Jenis: Article from Bulletin/Magazine
Dalam koleksi: Proceedings Institut Teknologi Bandung vol. 31 no. 3 (1999), page 91-97.
Topik: Electric Power Distribution System; Current Distortion; Phase Shifting Transformer; Harmonics Minimization
Fulltext: Syafrudin.PDF (604.87KB)
Ketersediaan
  • Perpustakaan Pusat (Semanggi)
    • Nomor Panggil: PP32
    • Non-tandon: 1 (dapat dipinjam: 0)
    • Tandon: tidak ada
    Lihat Detail Induk
Isi artikelThe increasing use of nonlinear loads has made the currents in power distribution system highly distorted with high level harmonic currents content (THD) and created serious harmonics problems. This paper proposed a new method to minimize current harmonics in power distribution system by using phase shifting auto-transformer. The loads of system are divided into two parts which are supplied by auto-transformer with 30o phase shifting. The effects of the phase shifting which causes harmonic currents are cancelled, and the resulting currents harmonic in power distribution system are minimized. Detailed mechanism of current harmonic minimization is presented. Several configurations of phase shifting auto-transformer are discussed and compared. The influence of load operating conditions are discussed. Experimental results are shown to verify this proposed method.